ecoCOOLING Combo Installation, Operating & Maintenance Manual
Doc Ref: Page 6 of 14
EcoCooling IOM Manual RevA
4 Design Data
4.1 General performance Data
** Rating capacity shown based on 131F return air temperature to cabinet in 131F ambient conditions at
nominal voltage and unimpeded resistance to air flow.
4.2 Summary of Basic Controls:
One Important Note: In order for air to air heat exchangers to cool the internal cabinet air,
the ambient air must be at a lower temperature than the internal cabinet return temperature.
All of these temperatures are monitored by the internal control boards located inside the
ecoCOOLING unit.
With the combo mode of operation, the air conditioner control board (USACG-6) operates
secondary to the heat exchanger control board (USHX2) which is the master control board.
The factory setting for the heat exchanger to operate alone is up to 35 Deg C internal return
temperature. Once the internal cabinet temperature reaches approx. 36 Deg C, the air
conditioner will come on. As long as the ambient is lower than 35 Deg C, the heat
exchanger and air conditioner will operate at the same time. Once the ambient is approx.
36 Deg C and an internal temperature is 36 Deg C or higher, the heat exchanger will turn
off. At this point the AC is operating on its own. The AC will continue to operate alone
until the ambient is lower than the internal temperature, and the internal temperature is
below 35 Deg C.